| 电源 | |
|---|---|
| Active/Passive I > 4 mA (for min. 100 ms) / I < 1.5 mA Open circuit voltage/short-circuit current 18 V / 5 mA | Active/Passive | I > 4 mA (for min. 100 ms) / I < 1.5 mA | Open circuit voltage/short-circuit current | 18 V / 5 mA |
| Contact loading 40 V DC Signal level 1-signal: (L+) -2.5 V (50 mA, short-circuit/overload proof) 0-signal: blocked output (off-state current ≤ 10 µA) | Contact loading | 40 V DC | Signal level | 1-signal: (L+) -2.5 V (50 mA, short-circuit/overload proof) 0-signal: blocked output (off-state current ≤ 10 µA) |
| Current range | 0 ... 20 mA or 4 ... 20 mA |
| Current range 0 ... 20 mA or 4 ... 20 mA Open loop voltage max. 24 V DC Load max. 650 Ω Fault signal downscale I ≤ 3.6 mA, upscale I ≥ 21.5 mA (acc. NAMUR NE43) | Current range | 0 ... 20 mA or 4 ... 20 mA | Open loop voltage | max. 24 V DC | Load | max. 650 Ω | Fault signal | downscale I ≤ 3.6 mA, upscale I ≥ 21.5 mA (acc. NAMUR NE43) |
| Input III, IV/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V eff |
| Interface/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V eff |
| Open circuit voltage/short-circuit current | 8.2 V / 10 mA |
| Open loop voltage | max. 24 V DC |
| Output III, IV/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V eff |
| Output V/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V eff |
| Power consumption | 2.5 W / 4 VA |
| Power dissipation | 2.2 W / 3.5 VA |
| Rated current | I r | approx. 130 mA |
| Rated voltage | U r | 20 ... 90 V DC / 48 ... 253 V AC 50 ... 60 Hz |
| 交流 / 直流特性 | |
| Accuracy | slip monitoring: 1% frequency measurement: 0.5% of measured value; but >0.001Hz |
| Contact loading 250 V AC / 2 A / cos φ ≥ 0.7 ; 40 DC / 2 A Mechanical life 5 x 10 7 switching cycles Energized/De-energized delay approx. 20 ms / approx. 20 ms | Contact loading | 250 V AC / 2 A / cos φ ≥ 0.7 ; 40 DC / 2 A | Mechanical life | 5 x 10 7 switching cycles | Energized/De-energized delay | approx. 20 ms / approx. 20 ms |
| Energized/De-energized delay | approx. 20 ms / approx. 20 ms |
| Input frequency | rotation direction monitoring 0.001 ... 1000 Hz slip monitoring 10 ... 1000 Hz |
| Resolution | slip monitoring: 1% frequency measurement: 0,1% of measured value; but >0.001Hz |
| Response delay | ≤ 200 ms |
| Response delay ≤ 200 ms | Response delay | ≤ 200 ms |
| 环境与封装 | |
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
| Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) (W x H x D) , housing type C2 |
| Height | 119 mm |
| Height 119 mm Width 40 mm Depth 115 mm | Height | 119 mm | Width | 40 mm | Depth | 115 mm |
| Influence of ambient temperature | 0.003 %/K (30 ppm) |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
| Resolution < 10 µA Accuracy < 30 µA Influence of ambient temperature 0.005 %/K (50 ppm) | Resolution | < 10 µA | Accuracy | < 30 µA | Influence of ambient temperature | 0.005 %/K (50 ppm) |
| 其他 | |
| Active/Passive | I > 4 mA (for min. 100 ms) / I < 1.5 mA |
| Configuration | via operating buttons via PACTware |
| Connection | terminals 23, 24 |
| Connection programming socket Interface RS 232 | Connection | programming socket | Interface | RS 232 |
| Connection side | field side |
| Contact loading | 250 V AC / 2 A / cos φ ≥ 0.7 ; 40 DC / 2 A |
| Control elements | Control panel |
| Degree of protection | IEC 60529:2001 |
| Depth | 115 mm |
| Directive 2014/30/EU | EN 61326-1:2006 |
| Directive 2014/30/EU EN 61326-1:2006 | Directive 2014/30/EU | EN 61326-1:2006 |
| Directive 2014/35/EU | EN 61010-1:2010 |
| Directive 2014/35/EU EN 61010-1:2010 | Directive 2014/35/EU | EN 61010-1:2010 |
| Display elements | LEDs , display |
| Electromagnetic compatibility | NE 21:2006 |
| Fault signal | downscale I ≤ 3.6 mA, upscale I ≥ 21.5 mA (acc. NAMUR NE43) |
| Input | EN 60947-5-6:2000 |
| Input I, II | 2-wire sensor, sensor acc. to EN 60947-5-6 (NAMUR) or mechanical contact |
| Input I, II/other circuits | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V eff |
| Interface | RS 232 |
| Interface/output III, IV | basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 V eff |
| Labeling | space for labeling at the front |
| Line fault detection | breakage I ≤ 0.15 mA; short-circuit I > 4 mA |
| Load | max. 650 Ω |
| Mass | 300 g |
| Measuring range | 0.001 ... 1000 Hz |
| Measuring time | frequency measurement: < 100 ms |
| Mechanical life | 5 x 10 7 switching cycles |
| Mutual output I, II, III | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V eff |
| Mutual output I, II, IV | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V eff |
| Output I, II | signal, relay |
| Output III and IV | signal , electronic output, passive |
| Output III, IV/input III, IV | basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 V eff |
| Output III, IV/V | basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 V eff |
| Output I, II/other circuits | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V eff |
| Output V | analog |
| Programming interface | programming socket |
| Pulse duration | min. 250 µs , overlap on direction of rotation signal: ≥ 125 µs |
| Signal level | 1-signal: (L+) -2.5 V (50 mA, short-circuit/overload proof) 0-signal: blocked output (off-state current ≤ 10 µA) |
| Signal type | Digital Input |
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
| Switching point/switching hysteresis | logic 1: > 2.5 mA ; logic 0: < 1.9 mA |
| Width | 40 mm |