71455

71455

在产

G10 ultra compact module, 4 outputs

查看国产替代问 AI FAE

全部替代型号

查看完整报告

技术参数

电源
Current loading capacity≤ 100 mA Total current , overload and short-circuit protected
Rated operating currentI e | ≤ 40 mA / max. 150 mA
Rated operating voltageU e | 18.5 ... 31.6 V from AS-Interface
Supplyfrom AS-Interface
Voltage≥ (U e - 7.0 V)
交流 / 直流特性
Noise immunityEN 61000-6-2:2005 EN 62026-2:2013
环境与封装
Ambient temperature-25 ... 70 °C (-13 ... 158 °F)
Contacts CuSn / Au Housing PBT PC Body PUR, black Cable PUR Mounting screw Stainless steel 1.4305 / AISI 303Contacts | CuSn / Au | Housing | PBT PC | Body | PUR, black | Cable | PUR | Mounting screw | Stainless steel 1.4305 / AISI 303
Height21.5 mm
Height 21.5 mm Width 27.7 mm Length 40.5 mmHeight | 21.5 mm | Width | 27.7 mm | Length | 40.5 mm
Mounting screwStainless steel 1.4305 / AISI 303
Storage temperature-25 ... 80 °C (-13 ... 176 °F)
其他
AS-InterfaceEN 62026-2:2013
AS-Interface specificationV3.0
BodyPUR, black
CablePUR
Colorblack
ConnectionAS-Interface: AS-Interface flat cable Outputs & matching connector: M12 connector, 5-pin, A-coded, acc. to IEC 61076-2-101:2012
ContactsCuSn / Au
Cores5 x 0.34 mm 2
D0- OUT1
D0 - OUT1 D1 - OUT2 D2 - OUT3 D3 - OUT4D0 | - OUT1 | D1 | - OUT2 | D2 | - OUT3 | D3 | - OUT4
D1- OUT2
D2- OUT3
D3- OUT4
Data bits (function via AS-Interface)Input Output
Degree of protectionEN 60529:2000
Directive 2014/30/EUEN 62026-2:2013
Directive 2014/30/EU EN 62026-2:2013Directive 2014/30/EU | EN 62026-2:2013
Electrical safetyIEC 61140:2004
Emitted interferenceEN 61000-6-4:2011
Fieldbus standardEN 62026-2:2013
HousingPBT PC
ID1 code7
ID2 code7
ID codeA
IO code7
LED AS-iAS-Interface voltage; LED green
LED FAULTerror display; LED red red: communication error or address is 0 red flashing: Output supply overload
LengthL | 1 m
Mass81 g
MTBF382 a
Node typeA/B node
Number/Type4 electronic outputs, PNP, overload and short-circuit proof
P0communication monitoring P0 = 1 (default settings), monitoring = ON, i.e. if communication fails, the outputs are de-energised P0 = 0, monitoring = OFF, if communication fails, the outputs maintain their condition
P1not used
P2Synchronous mode P2 = 0 synchronous mode on P2 = 1 synchronous mode off (default settings)
P3not used
Parameter bits (programmable via AS-i)function
ProfileS-7.A.7
Protection classIII
Required gateway specificationV3.0
Sheath diameter∅4.8 mm
Sheath diameter ∅4.8 mm Color black Cores 5 x 0.34 mm 2 Length L 1 mSheath diameter | ∅4.8 mm | Color | black | Cores | 5 x 0.34 mm 2 | Length | L | 1 m
Shock and impact resistance30 g , 11 ms in 6 spatial directions 3 shocks 10 g , 16 ms in 6 spatial directions 1000 shocks
Surge protectionU e : Over voltage category III, safe isolated power supplies (PELV)
Tightening torque, cable gland0.4 Nm
Tightening torque, fastening screws1.65 Nm
UL approvalcULus Listed, Type 1 enclosure
UL File NumberE223772 "For use in NFPA 79 Applications only"
Vibration resistance0.75 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles
Width27.7 mm

器件图片

技术资料

该型号暂未收录资料。