Поиск аналогов электронных компонентов
104147
Pepperl+Fuchs, Inc.Германия

104147

Производится

Inductive sensor

Подобрать аналогСпросить AI FAE

Все аналоги

Полный отчёт

Технические параметры

Питание
Measuring plate not detected ≥ 3 mA at nominal voltage Measuring plate detected ≤ 1 mA at nominal voltageMeasuring plate not detected | ≥ 3 mA at nominal voltage | Measuring plate detected | ≤ 1 mA at nominal voltage
Nominal voltageU o | 8 V
Operating voltageU B | 5 ... 25 V
Характеристики по постоянному и переменному току
Switching frequencyf | 0 ... 5000 Hz
Условия эксплуатации и корпус
Ambient temperature-25 ... 100 °C (-13 ... 212 °F)
Другое
ANZEx18.3018X
Assured operating distances a | 0 ... 0.65 mm
Bending radius> 10 x cable diameter
Cable diameter2.6 mm ± 0.2 mm
Cable diameter 2.6 mm ± 0.2 mm Bending radius > 10 x cable diameter Material PVC Core cross section 0.14 mm 2 Length L 10 mCable diameter | 2.6 mm ± 0.2 mm | Bending radius | > 10 x cable diameter | Material | PVC | Core cross section | 0.14 mm 2 | Length | L | 10 m
CML approvalon request
Connection typecable
Control drawing116-0452
Core cross section0.14 mm 2
Degree of protectionIP67
Diagnostic Coverage (DC)0 %
Diameter5 mm
Equipment protection level DaIECEx PTB 11.0037X
Equipment protection level GaIECEx PTB 11.0037X
Equipment protection level Ga PTB 00 ATEX 2048 X Equipment protection level Gb PTB 00 ATEX 2048 X Equipment protection level Da PTB 00 ATEX 2048 XEquipment protection level Ga | PTB 00 ATEX 2048 X | Equipment protection level Gb | PTB 00 ATEX 2048 X | Equipment protection level Da | PTB 00 ATEX 2048 X
Equipment protection level GbIECEx PTB 11.0037X
Equipment protection level MbIECEx PTB 11.0037X
Hazardous LocationE501628
Hazardous Location 19-AV4BO-0025XHazardous Location | 19-AV4BO-0025X
Hazardous Location 2020322315002256Hazardous Location | 2020322315002256
Housing materialStainless steel 1.4305 / AISI 303
HysteresisH | typ. %
Installationflush
LengthL | 10 m
Length 20 mm Diameter 5 mmLength | 20 mm | Diameter | 5 mm
MaterialPVC
Measuring plate detected≤ 1 mA at nominal voltage
Measuring plate not detected≥ 3 mA at nominal voltage
Mission Time (T M )20 a
MTTF d1050 a
NAMUREN 60947-5-6:2000 IEC 60947-5-6:1999
NAMUR EN 60947-5-6:2000 IEC 60947-5-6:1999 Standards EN IEC 60947-5-2NAMUR | EN 60947-5-6:2000 IEC 60947-5-6:1999 | Standards | EN IEC 60947-5-2
Ordinary LocationE87056
Ordinary Location E87056 Hazardous Location E501628 Control drawing 116-0452Ordinary Location | E87056 | Hazardous Location | E501628 | Control drawing | 116-0452
Output typeNAMUR
Rated operating distances n | 0.8 mm
Reduction factor r 3040.85
Reduction factor r Al0.4
Reduction factor r Cu0.3
Safety Integrity Level (SIL)SIL 2
Scope of deliverySupplied with 2 nuts
Sensing facePBT
StandardsEN IEC 60947-5-2
Suitable for 2:1 technologyyes , Reverse polarity protection diode not required
Switching functionNormally closed (NC)
UL approvalcULus Listed Circuitry: Class 2 Power Source Enclosure Type Rating: Type 1 Supply/Switching Voltage: 8.2 V DC
Use in the hazardous areasee instruction manuals

Изображения

Документы