G16 compact module, 4 inputs (PNP)

Спросить AI FAE

Все аналоги

Полный отчёт

Технические параметры

Питание
Current loading capacity≤ 200 mA (T B ≤ 40 °C), ≤ 150 mA (T B ≤ 70 °C), overload-proof and short-circuit protected
Input current≤ 9 mA (limited internally)
Rated operating currentI e | ≤ 40 mA (without sensors) / max. 240 mA
Rated operating voltageU e | 26.5 ... 31.6 V from AS-Interface
Supplyfrom AS-Interface
Voltage21 ... 31 V
Характеристики по постоянному и переменному току
Noise immunityEN 61000-6-2:2005 EN 62026-2:2013
Signal delay< 1 ms (input/AS-Interface)
Условия эксплуатации и корпус
Ambient temperature-25 ... 70 °C (-13 ... 158 °F)
Height29.35 mm
Height 29.35 mm Width 30 mm Length 103 mmHeight | 29.35 mm | Width | 30 mm | Length | 103 mm
Mountingscrew mounting
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Другое
0 (unattenuated)≤ 3 mA
0 (unattenuated) ≤ 3 mA 1 (attenuated) ≥ 5 mA0 (unattenuated) | ≤ 3 mA | 1 (attenuated) | ≥ 5 mA
1 (attenuated)≥ 5 mA
Altitude≤ 2000 m above MSL
AS-InterfaceEN 62026-2:2013
AS-Interface specificationV3.0
Climatic conditionsFor indoor use only
ConnectionAS-Interface: M12 x 1 quick disconnect actuators: M8 x 1 quick disconnect
Degree of protectionEN 60529:2000
Directive 2014/30/EUEN 62026-2:2013 EN 61000-6-2:2005, EN 61000-6-4:2007
Directive 2014/30/EU EN 62026-2:2013 EN 61000-6-2:2005, EN 61000-6-4:2007Directive 2014/30/EU | EN 62026-2:2013 EN 61000-6-2:2005, EN 61000-6-4:2007
Emitted interferenceEN 61000-6-4:2007
Fieldbus standardEN 62026-2:2013
HousingPBT
Housing PBTHousing | PBT
ID1 code7
ID2 code0
ID codeA
InputEN 61131-2
IO code0
IO code 0 ID code A ID1 code 7 ID2 code 0IO code | 0 | ID code | A | ID1 code | 7 | ID2 code | 0
LED INswitching state (input); 4 LED yellow
LED PWR/FAULTStatus display; multi-colour LED Green: normal operation Red: communication fault Flashing yellow/red: address 0 Flashing green/red: sensor supply overload
Length103 mm
Mass100 g
Node typeA/B node
Number/Type4 inputs for 2- or 3-wire sensors (PNP), DC
Pollution degree3
ProfileS-0.A.0
Protection classIII
Relative humidity85 % , non-condensing
Required gateway specification≥ V2.1
Shock and impact resistance30 g , 11 ms in 6 spatial directions 3 shocks 10 g , 16 ms in 6 spatial directions 1000 shocks
Surge protectionU e : Over voltage category III, safe isolated power supplies (PELV)
Switching pointaccording to DIN EN 61131-2 (Type 2)
Tightening torque, cable gland0.4 Nm (M12 connector), 0.2 Nm (M8 connector)
UL File NumberE223772
Vibration resistance0.75 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles
Width30 mm