Поиск аналогов электронных компонентов
85510
Pepperl+Fuchs, Inc.Германия

85510

Производится

Power hub motherboard for Yokogawa ALF111

Спросить AI FAE

Все аналоги

Полный отчёт

Технические параметры

Питание
Fieldbus segment/Supplyfunctional insulation acc. to IEC 62103, rated insulation voltage 250 V eff
Power dissipationtyp. 0.4 W per segment
Rated currentI r | 12 A
Rated voltageU r | 19.2 ... 35 V SELV/PELV
Условия эксплуатации и корпус
Ambient temperature-40 ... 70 °C (-40 ... 158 °F)
Design / MountingMotherboard based
MountingDIN rail mounting
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Другое
Approved forClass I, Division 2, Groups A, B, C, D, T4 / Class I, Zone 2, AEx/Ex nA IIC T4 , AEx/Ex ec IIC T4
Approved for Ex ec IIC T4 GcApproved for | Ex ec IIC T4 Gc
CertificateTÜV 10 ATEX 555761X
Connectionredundant
Connection typescrew terminal , pluggable
Core cross sectionscrew terminals: 0.25 ... 2.5 mm 2 spring terminals: 0.25 ... 1.5 mm 2
Corrosion resistanceacc. to ISA-S71.04-1985, severity level G3
Degree of protectionIEC 60529
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)Directive 2014/30/EU | EN 61326-1:2013 (industrial locations)
Directive 2014/34/EUEN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
Directive 2014/34/EU EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
Electromagnetic compatibilityNE 21:2012
Fault signalVFC alarm 1 A, 50 V DC, normally closed
Fieldbus segment/Fieldbus segmentfunctional insulation acc. to IEC 62103, rated insulation voltage 50 V eff
Fieldbus standardIEC 61158-2
FM approvalCoC 3024816, CoC 3024816C
FM certificateFM 19 US 0015 X and FM 19 CA 0011 X
FM markingAEx/Ex ec IIC T4
Host-sideYokogawa ALF111 for AKB336 interface cable
Housing materialPolycarbonate
IECEx approvalIECEx TUN 13.0037X
Installation in hazardous areaZone 2 / Div. 2
Marine approvalDNV A-14038, pending for MBHC-FB-4R.YO.R
MarkingII 3G Ex ec IIC T4 Gc
Marking II 3G Ex ec IIC T4 GcMarking | II 3G Ex ec IIC T4 Gc
Massapprox. 610 g
Number of segments4 Redundant Power Supply
Pollution degreemax. 2, according to IEC 60664
Relative humidity< 95 % non-condensing
Shock resistanceEN 60068-2-27
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Terminating resistor100 Ω integrated
Vibration resistanceEN 60068-2-6

Изображения

Документы

К этому компоненту пока не привязаны документы.