kl1352
ПроизводитсяThe KL1352 digital input terminal analyzes the input signal of NAMUR sensors according to IEC 60947-5-6. The Bus Terminal has two channels. In addition...
Все аналоги
Полный отчётТехнические параметры
| Питание | |
|---|---|
| Current consumption K-bus | typ. 70 mA |
| Current load power contacts | I max : 10 A |
| Open circuit voltage | typ. 8.2 V DC |
| Short-circuit current | typ. 8.2 mA |
| Signal current “0” | ≤ 1.2 mA |
| Signal current “1” | ≥ 2.1 mA |
| Условия эксплуатации и корпус | |
| Dimensions (W x H x D) | 12 mm x 100 mm x 68 mm |
| Operating temperature | 0…55°C |
| Side by side mounting by means of | double slot and key connection |
| Storage temperature | -25…+85°C |
| Другое | |
| Approvals/markings | CE, CCC, UL, ATEX, IECEx, DNV, cFMus |
| Bit width in the process image | 4 inputs |
| Configuration | no address or configuration setting |
| Connection technology | 2-wire |
| Electrical isolation | 500 V (K-bus/field potential) |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Ex marking | ATEX: II 3G Ex ec IIC T4 Gc IECEx: Ex ec IIC T4 Gc cFMus: Class I, Division 2, Groups A, B, C, D Class I, Zone 2, AEx ec IIC T4 Gc |
| Input filter | 3 ms |
| Installation | on 35 mm DIN rail, conforming to EN 60715 with lock |
| KL1352 | Bus Terminal, 2-channel digital input, NAMUR |
| KS1352 | Bus Terminal, 2-channel digital input, NAMUR, pluggable wiring level |
| Marking | labeling of the BZxxxx series |
| Material | polycarbonate |
| Number of inputs | 2 |
| Pluggable wiring level | for all KSxxxx Bus Terminals |
| Protect. rating/installation pos. | IP20/variable |
| Relative humidity | 95%, no condensation |
| Short-circuit detection | > 6.5 mA |
| Special features | NAMUR |
| Specification | NAMUR |
| Switching hysteresis | 0.2 mA |
| Technical data | KL1352 |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| Weight | approx. 55 g |
| Wiring | solid conductor (s), flexible conductor (st) and ferrule (f): spring actuation by screwdriver |