Технические параметры

Питание
Current consumption K-bustyp. 5 mA
Current consumption power contactstyp. 15 mA + load
Current load power contactsI max : 10 A
Max. output current0.5 A (short-circuit proof) per channel
Nominal voltage24 V DC (-15%/+20%)
Short-circuit current< 2 A
Условия эксплуатации и корпус
Dimensions (W x H x D)12 mm x 100 mm x 68 mm
Operating temperature0…55°C
Side by side mounting by means ofdouble slot and key connection
Storage temperature-25…+85°C
Другое
Approvals/markingsCE, CCC, UL, ATEX, IECEx, cFMus
Bit width in the process image2 outputs
Configurationno address or configuration setting
Connection technology4-wire
Electrical isolation500 V (K-bus/field potential)
EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4
Ex markingATEX: II 3G Ex ec IIC T4 Gc IECEx: Ex ec IIC T4 Gc cFMus: Class I, Division 2, Groups A, B, C, D Class I, Zone 2, AEx ec IIC T4 Gc
Installationon 35 mm DIN rail, conforming to EN 60715 with lock
KL2012Bus Terminal, 2-channel digital output, 24 V DC, 0.5 A
KS2012Bus Terminal, 2-channel digital output, 24 V DC, 0.5 A, pluggable wiring level
Load typeohmic, inductive, lamp load
Markinglabeling of the BZxxxx series
Materialpolycarbonate
Number of outputs2
Pluggable wiring levelfor all KSxxxx Bus Terminals
Protect. rating/installation pos.IP20/variable
Relative humidity95%, no condensation
Reverse polarity protection–
Switching-off energy< 150 mJ/channel
Technical dataKL2012
Vibration/shock resistanceconforms to EN 60068-2-6/EN 60068-2-27
Weightapprox. 55 g
Wiringsolid conductor (s), flexible conductor (st) and ferrule (f): spring actuation by screwdriver

Изображения