Питание
Active/Passive I > 4 mA (for min. 100 ms) / I < 1.5 mA Open circuit voltage/short-circuit current 18 V / 5 mAActive/Passive | I > 4 mA (for min. 100 ms) / I < 1.5 mA | Open circuit voltage/short-circuit current | 18 V / 5 mA
Contact loading 40 V DC Signal level 1-signal: (L+) -2.5 V (50 mA, short-circuit/overload proof) 0-signal: blocked output (off-state current ≤ 10 µA)Contact loading | 40 V DC | Signal level | 1-signal: (L+) -2.5 V (50 mA, short-circuit/overload proof) 0-signal: blocked output (off-state current ≤ 10 µA)
Current range0 ... 20 mA or 4 ... 20 mA
Current range 0 ... 20 mA or 4 ... 20 mA Open loop voltage max. 24 V DC Load max. 650 Ω Fault signal downscale I ≤ 3.6 mA, upscale I ≥ 21.5 mA (acc. NAMUR NE43)Current range | 0 ... 20 mA or 4 ... 20 mA | Open loop voltage | max. 24 V DC | Load | max. 650 Ω | Fault signal | downscale I ≤ 3.6 mA, upscale I ≥ 21.5 mA (acc. NAMUR NE43)
Input III, IV/power supplyreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V eff
Interface/power supplyreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V eff
Open circuit voltage/short-circuit current8.2 V / 10 mA
Open loop voltagemax. 24 V DC
Output III, IV/power supplyreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V eff
Output V/power supplyreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V eff
Power consumption2.5 W / 4 VA
Power dissipation2.2 W / 3.5 VA
Rated currentI r | approx. 130 mA
Rated voltageU r | 20 ... 90 V DC / 48 ... 253 V AC 50 ... 60 Hz
Характеристики по постоянному и переменному току
Accuracyslip monitoring: 1% frequency measurement: 0.5% of measured value; but >0.001Hz
Contact loading 250 V AC / 2 A / cos φ ≥ 0.7 ; 40 DC / 2 A Mechanical life 5 x 10 7 switching cycles Energized/De-energized delay approx. 20 ms / approx. 20 msContact loading | 250 V AC / 2 A / cos φ ≥ 0.7 ; 40 DC / 2 A | Mechanical life | 5 x 10 7 switching cycles | Energized/De-energized delay | approx. 20 ms / approx. 20 ms
Energized/De-energized delayapprox. 20 ms / approx. 20 ms
Input frequencyrotation direction monitoring 0.001 ... 1000 Hz slip monitoring 10 ... 1000 Hz
Resolutionslip monitoring: 1% frequency measurement: 0,1% of measured value; but >0.001Hz
Response delay≤ 200 ms
Response delay ≤ 200 msResponse delay | ≤ 200 ms
Условия эксплуатации и корпус
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Dimensions40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) (W x H x D) , housing type C2
Height119 mm
Height 119 mm Width 40 mm Depth 115 mmHeight | 119 mm | Width | 40 mm | Depth | 115 mm
Influence of ambient temperature0.003 %/K (30 ppm)
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Resolution < 10 µA Accuracy < 30 µA Influence of ambient temperature 0.005 %/K (50 ppm)Resolution | < 10 µA | Accuracy | < 30 µA | Influence of ambient temperature | 0.005 %/K (50 ppm)
Другое
Active/PassiveI > 4 mA (for min. 100 ms) / I < 1.5 mA
Configurationvia operating buttons via PACTware
Connectionterminals 23, 24
Connection programming socket Interface RS 232Connection | programming socket | Interface | RS 232
Connection sidefield side
Contact loading250 V AC / 2 A / cos φ ≥ 0.7 ; 40 DC / 2 A
Control elementsControl panel
Degree of protectionIEC 60529:2001
Depth115 mm
Directive 2014/30/EUEN 61326-1:2006
Directive 2014/30/EU EN 61326-1:2006Directive 2014/30/EU | EN 61326-1:2006
Directive 2014/35/EUEN 61010-1:2010
Directive 2014/35/EU EN 61010-1:2010Directive 2014/35/EU | EN 61010-1:2010
Display elementsLEDs , display
Electromagnetic compatibilityNE 21:2006
Fault signaldownscale I ≤ 3.6 mA, upscale I ≥ 21.5 mA (acc. NAMUR NE43)
InputEN 60947-5-6:2000
Input I, II2-wire sensor, sensor acc. to EN 60947-5-6 (NAMUR) or mechanical contact
Input I, II/other circuitsreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V eff
InterfaceRS 232
Interface/output III, IVbasic insulation according to IEC/EN 61010-1, rated insulation voltage 50 V eff
Labelingspace for labeling at the front
Line fault detectionbreakage I ≤ 0.15 mA; short-circuit I > 4 mA
Loadmax. 650 Ω
Mass300 g
Measuring range0.001 ... 1000 Hz
Measuring timefrequency measurement: < 100 ms
Mechanical life5 x 10 7 switching cycles
Mutual output I, II, IIIreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V eff
Mutual output I, II, IVreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V eff
Output I, IIsignal, relay
Output III and IVsignal , electronic output, passive
Output III, IV/input III, IVbasic insulation according to IEC/EN 61010-1, rated insulation voltage 50 V eff
Output III, IV/Vbasic insulation according to IEC/EN 61010-1, rated insulation voltage 50 V eff
Output I, II/other circuitsreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V eff
Output Vanalog
Programming interfaceprogramming socket
Pulse durationmin. 250 µs , overlap on direction of rotation signal: ≥ 125 µs
Signal level1-signal: (L+) -2.5 V (50 mA, short-circuit/overload proof) 0-signal: blocked output (off-state current ≤ 10 µA)
Signal typeDigital Input
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Switching point/switching hysteresislogic 1: > 2.5 mA ; logic 0: < 1.9 mA